Описание оборудования | |
---|---|
G12 flat module 4 inputs (PNP) and 4electronic outputs | |
General specifications | |
Slave type | A/B slave |
AS-Interface specification | V3.0 |
Required master specification | ? V3.0 |
UL File Number | E223772 |
Functional safety related parameters | |
MTTFd | 180 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Indicators/operating means | |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
LED IN | switching state (input); 4 LED yellow |
LED OUT | Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload |
Electrical specifications | |
Auxiliary voltage (output) | 24 V DC ± 15 % PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ? 40 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
Input | |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
Supply | from external auxiliary voltage UEXT |
Current loading capacity | ? 600 mA overload and short-circuit resistant |
Input current | ? 8 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
Signal delay | < 1 ms (input/AS-Interface) |
Output | |
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Current | 2 A per output 6 A total (TB ? 40 °C) 4 A total (TB ? 70 °C) |
Voltage | ? (UAUX - 0.5 V) |
Directive conformity | |
Electromagnetic compatibility | |
Standard conformity | |
Degree of protection | EN60529:2000 |
Fieldbus standard | EN62026-2:2013 |
Input | EN 61131-2 |
Emitted interference | EN61000-6-4:2007 |
AS-Interface | EN62026-2:2013 |
Noise immunity | EN61000-6-2:2005 EN62026-2:2013 |
Programming instructions | |
Profile | S-7.A.7 |
IO code | 7 |
ID code | A |
ID1 code | 7 |
ID2 code | 7 |
Data bits (function via AS-Interface) | input output |
Parameter bits (programmable via AS-i) | function |
Ambient conditions | |
Ambient temperature< |